NIST Test Fans the Flames for High-Rise Fire Safety

Nov 22, 2006
NIST Test Fans the Flames for High-Rise Fire Safety
Members of a research team watch flames erupt from an abandoned Chicago apartment building during a Nov. 10 test of positive pressure ventilation in high-rise fires. Red truck (lower right corner) is a mobile ventilation system blowing air through the front door of the test building to keep the corridors and stairwells passable, while forcing the fire outside. Credit: NIST

Reseearchers from NIST, the Chicago Fire Department and the Chicago Housing Authority recently set controlled fires in an abandoned Chicago apartment building to test a new fire-fighting technique -- using powerful fans to force smoke and heat from corridors and stairwells so that they stay passable and safe for both escaping occupants and firefighters.

The blow-torch-like flames erupting from the windows of an abandoned, 16-story Chicago apartment building on Nov. 10 were certainly dramatic to watch from the street below. However, for a team of investigators from the Chicago Fire Department (CFD), the Chicago Housing Authority (CHA) and the National Institute of Standards and Technology (NIST), the real excitement was what was happening to the environment inside the building’s corridors and stairwells.

The controlled fires on the third, 10th and 15th floors of the Windy City high-rise were part of a real-world laboratory experiment to study the effectiveness in multistory buildings of positive pressure ventilation (PPV). PPV is the use of powerful fans during fires to force smoke and heat from corridors and stairwells so that they stay passable and safe for both escaping occupants and entering emergency responders. In past events—such as the October 2003 blaze in a government building in Chicago where six people died—fire flow into corridors and stairwells often has resulted in tragedy.

Eleven NIST researchers worked with more than 70 CFD and CHA staff for the two weeks prior to the experiment to prepare the building. All 16 floors were equipped with temperature and pressure monitors while the three burn floors also included cameras, heat flux gauges and typical apartment furnishings. The entire setup was connected to the data acquisition center by seven miles of cable.

Once the fires were under way, a variety of ventilation tests were conducted. For example, in one test, a large fan was placed at the front door to force cool air up through the building. In another test, two smaller fans—one on the first floor and one two floors below the fire floor, both forcing air into the stairwell—were used to achieve the same PPV effect. Preliminary results from both scenarios show that PPV significantly reduced the temperature and amount of smoke in the corridors and stairwells outside the burn rooms. In one case, the temperature quickly dropped from 316 degrees Celsius to 16 degrees (600 degrees Fahrenheit to 60).

A NIST report on the tests is expected to be released in the spring of 2007.

Source: National Institute of Standards and Technology (NIST)

Explore further: Future phones to use blood and speech to monitor HIV, stress, nutrition

add to favorites email to friend print save as pdf

Related Stories

The ABC's of animal speech: Not so random after all

1 hour ago

The calls of many animals, from whales to wolves, might contain more language-like structure than previously thought, according to study that raises new questions about the evolutionary origins of human language.

New type of solar concentrator desn't block the view

11 hours ago

(Phys.org) —A team of researchers at Michigan State University has developed a new type of solar concentrator that when placed over a window creates solar energy while allowing people to actually see through ...

Cities, states face off on municipal broadband

11 hours ago

Wilson, N.C., determined nearly a decade ago that high-speed Internet access would be essential to the community's social and economic health in the 21st century, just as electricity, water and sewers were in the previous ...

Recommended for you

Neuron circuit may enable pitch perception applications

16 hours ago

The first FitzHugh-Nagumo neuron circuit designed to include noise and exhibit the Ghost Stochastic Resonance effect has been presented by researchers from Université de Bourgogne in France. Their circuit ...

Knee-deep sensing

18 hours ago

A new, non-invasive technique to track the motion of knee bones in 3D with a very high precision has been presented by researchers in Australia. By employing a single-element ultrasound sensor and a fast ...

User comments : 0