Smoke Alarms + Sprinklers + Closed Doors = Lives Saved in Dorm Fires

March 31, 2010
These post-fire photographs of the dorm rooms show the difference a sprinkler makes. There is little visible damage the in the top photo that had a sprinkler in the room; there was no sprinkler in the dorm room in the lower picture. Credit: NIST

( -- Experimenting on a university dormitory that was scheduled to be torn down, fire researchers from the National Institute of Standards and Technology have demonstrated that the correct combination of automatic fire sprinkler systems, smoke alarms and closed doors provided enough time and safe conditions for residents to escape safely and for firefighters to perform their job without undue hazard.

The study’s goal was to compare the hazard levels created by room fires in dormitory buildings with and without sprinklers in the room where the starts. Researchers used a dorm at the University of Arkansas in Fayetteville, Ark., that was scheduled to be replaced with a high-rise building.

Fires create many potentially fatal hazards, including high heat, loss of visibility and—what can be the most critical risk—toxic gases. In addition to monitoring thermal conditions and visibility, researchers also measured the oxygen, carbon monoxide and carbon dioxide levels to determine the tenability, that is, survival conditions, on the fire floor.

The five rooms used in the experiment were furnished as typical dorms are and included clothing, books and furniture. Smoke alarms were installed in the rooms and the corridors. The smoke alarms activated within 30 seconds of ignition of a trash container in a dorm room.

Experiments 1 and 2 were conducted with the dorm room door and windows closed and in both the experiments the corridor remained tenable, which would allow other students to exit safely past the room. Rooms for experiments 2 and 3 had automatic fire sprinklers installed. The automatic fire sprinklers activated within two minutes after ignition in both experiments. In the sprinklered experiments, tenability was maintained in the dorm room and the corridor.

Experiments 4 and 5 were conducted with the door of the dorm room open and no active sprinkler. In both experiments the tenability limits were exceeded in the dorm room and corridor.

“This study demonstrated the value of balanced fire safety design,” says NIST Fire Protection Engineer Dan Madrzykowski. “The results show the potential life safety benefits of smoke alarms, compartmentation and automatic fire sprinkler systems in college dormitories and similar occupancies.”

The experiments also demonstrated the importance of a closed door between the fire room and corridor in limiting the spread of smoke and gasses to other areas of the building.

The studied was performed as part of the U.S. Fire Administration’s initiative to improve fire safety in college housing and in collaboration with the University of Arkansas and the Fayetteville Fire Department.

Another series of experiment was conducted with fires starting in a day room area open to the dormitory corridor. The results of the two studies were published in “Impact of Sprinklers on the Fire Hazard in Dormitories: Sleeping Room Fire Experiments” (NIST Technical Note 1658, available at and “Impact of Sprinklers on the Fire hazard in Dormitories: Day Room Fire Experiments” (NISTIR 7120, available at

Explore further: NASA develops new airplane fire sensor

Related Stories

NASA develops new airplane fire sensor

July 20, 2005

NASA Wednesday announced the development of a new generation of fire detectors designed to significantly reduce the rate of false alarms aboard airliners.

'Smart' Buildings to Guide Future First Responders

November 3, 2005

NIST researchers are studying how "intelligent" building systems can be used by firefighters, police and other first responders to accurately assess emergency conditions in real-time. One of the biggest problems faced by ...

NIST Test Fans the Flames for High-Rise Fire Safety

November 22, 2006

Reseearchers from NIST, the Chicago Fire Department and the Chicago Housing Authority recently set controlled fires in an abandoned Chicago apartment building to test a new fire-fighting technique -- using powerful fans to ...

NIST releases final WTC 7 investigation report

November 20, 2008

The National Institute of Standards and Technology (NIST) today released its final report on the Sept. 11, 2001, collapse of the 47-story World Trade Center building 7 (WTC 7) in New York City. The final report is strengthened ...

Recommended for you

From a very old skeleton, new insights on ancient migrations

October 9, 2015

Three years ago, a group of researchers found a cave in Ethiopia with a secret: it held the 4,500-year-old remains of a man, with his head resting on a rock pillow, his hands folded under his face, and stone flake tools surrounding ...

Mexican site yields new details of sacrifice of Spaniards

October 9, 2015

It was one of the worst defeats in one of history's most dramatic conquests: Only a year after Hernan Cortes landed in Mexico, hundreds of people in a Spanish-led convey were captured, sacrificed and apparently eaten.

Ancient genome from Africa sequenced for the first time

October 8, 2015

The first ancient human genome from Africa to be sequenced has revealed that a wave of migration back into Africa from Western Eurasia around 3,000 years ago was up to twice as significant as previously thought, and affected ...

1 comment

Adjust slider to filter visible comments by rank

Display comments: newest first

not rated yet Apr 01, 2010
NIST tarnished rep on fire investigation since they dropped the 911 ball remains a concern - these clowns have no credibility but this conclusion is incipid and known - not real new research.

Please sign in to add a comment. Registration is free, and takes less than a minute. Read more

Click here to reset your password.
Sign in to get notified via email when new comments are made.