Circuit-breaker detects all types of fault currents

May 11, 2005

The new universal-current-sensitive Type B residual-current circuit-breaker (r.c.c.b.) from Siemens Automation and Drives (A&D) can detect pulsating and smooth DC fault currents as well as sinusoidal AC fault currents. These new circuit-breakers are designed for rated currents of 25 to 80 A. Thanks to its tripping range, the r.c.c.b. is also suitable for applications in which medical protection must be guaranteed against dangerous ventricular fibrillation. Typical areas of application for the universal-current-sensitive Type B residual-current circuit-breaker include medical equipment, machine tools, charging stations, test systems, and laboratory equipment.

With the Type B residual-current circuit-breaker (r.c.c.b.), Siemens A&D offers a "universal-current-sensitive" circuit breaker. This circuit-breaker is suitable for plants in which smooth DC fault currents can occur as well as AC fault currents and pulsating fault currents. In this, it goes beyond the performance range of its predecessor, the Type A r.c.c.b.

Smooth DC fault currents occur, for example, when operating frequency converters in cranes, machine controllers, elevator systems, and also in medical equipment such as computer tomographs. Tripping conditions up to 2 kHz are stipulated for these applications. For the rated fault current of 30 mA, the tripping range of the universal-current-sensitive r.c.c.b. is significantly under the limit curve for protection against dangerous ventricular fibrillation.

In detection, analysis and shutdown, the universal-current-sensitive r.c.c.b. works independently of a line voltage in accordance with VDE 0664 Part 100 and the requirements for Type A. A voltage supply is only required for detecting smooth DC fault currents. The function is fulfilled in all mains cables from a value of 50 V. This also provides maximum safety for the voltage-dependent section. Even if only one of the conductors is live and a fault current occurs, protection is established through the line-voltage-independent tripping function of the pulsating-current-sensitive device section.

Thanks to grading of the r.c.c.b. according to the rated fault currents 30 mA, 300 mA and 500 mA, there is a suitable device available for every protection level. In extensive plants, it is also possible to connect the circuit-breakers in series.

Explore further: Britain threatens Internet 'trolls' with two years in jail

add to favorites email to friend print save as pdf

Related Stories

Google profit dips to $2.8 bn

8 hours ago

Google said Thursday its profit in the past quarter dipped slightly from a year earlier, even as revenues for the technology giant showed a sharp increase.

Shrinking resource margins in Sahel region of Africa

9 hours ago

The need for food, animal feed and fuel in the Sahel belt is growing year on year, but supply is not increasing at the same rate. New figures from 22 countries indicate falling availability of resources per ...

Recommended for you

First-of-a-kind supercritical CO2 turbine

1 minute ago

Toshiba Corporation today announced that it will supply a first-of-a-kind supercritical CO2 turbine to a demonstration plant being built in Texas, USA. The plant will be developed by NET Power, LLC, a U.S. venture, together w ...

Japan firm showcases Bat-Signal of the future

1 hour ago

A free-floating image created by firing lasers into thin air was unveiled in Japan on Monday, offering the possibility one day of projecting messages into a cloudless sky, as seen in Batman.

Kickstarter suspends privacy router campaign

1 hour ago

Kickstarter has suspended an anonymizing router from its crowdfunding site. By Sunday, the page for "anonabox: A Tor hardware router" carried an extra word "(Suspended)" in parentheses with a banner below ...

User comments : 0