NIST corrosion lab tests suggest need for underground gas tank retrofits

Jul 30, 2014 by Laura Ost
NIST corrosion lab tests suggest need for underground gas tank retrofits
A NIST study found that corrosion may pose a hazard at underground gas storage tanks at filling stations. The study focused on sump pump components, especially the pump casings (labelled #3 in graphic), which are typically made of steel or cast iron. Credit: Environmental Protection Agency

A hidden hazard lurks beneath many of the roughly 156,000 gas stations across the United States.

The hazard is corrosion in parts of underground gas storage tanks—corrosion that could result in failures, leaks and contamination of groundwater, a source of drinking water. In recent years, field inspectors in nine states have reported many rapidly corroding gas storage tank components such as sump pumps. These incidents are generally associated with use of gasoline-ethanol blends and the presence of bacteria, Acetobacter aceti, which convert ethanol to acetic acid, a component of vinegar.

Following up on the inspectors' findings, a National Institute of Standards and Technology (NIST) laboratory study* has demonstrated severe corrosion—rapidly eating through 1 millimeter of wall thickness per year—on steel alloy samples exposed to ethanol and acetic acid vapors. Based on this finding, NIST researchers suggest may need to replace submersible pump casings, typically made of steel or cast iron, sooner than expected. Such retrofits could cost an estimated $1,500 to $2,500 each, and there are more than 500,000 underground gas storage tanks around the country.

NIST corrosion lab tests suggest need for underground gas tank retrofits
Optical micrographs of severe corrosion on steel alloy samples exposed to ethanol and acetic acid vapors -- conditions typical of underground gas storage tanks -- after 355 hours, 643 hours, and 932 hours. Credit: NIST

The NIST study focused only on sump pump components, located directly below access covers at filling stations, just above and connected to underground tanks. The sump pumps move fuel from underground tanks to the fuel dispensers that pump gas into cars. These underground tanks and pipes also may be made of steel and could be vulnerable, too. "We know there are corrosion issues associated with the inside of some tanks. We're not sure, at this point, if that type of corrosion is caused by the bacteria," NIST co-author Jeffrey Sowards says.

Much of the U.S. fuel infrastructure was designed for unblended gasoline. Ethanol, an alcohol that can be made from corn, is now widely used as a gasoline additive due to its oxygen content and octane rating, or antiknock index. A previous NIST study found that ethanol-loving bacteria accelerated pipeline cracking.**

For the latest study, NIST researchers developed new test methods and equipment to study copper and steel alloy samples either immersed in ethanol-water solutions inoculated with bacteria, or exposed to the vapors above the medium—conditions mimicking those around sump pumps. Corrosion rates were measured over about 30 days.

The NIST study confirmed damage similar to that seen on sump pumps by field inspectors. The worst damage, with flaky iron oxide products covering corrosion, was found on steel exposed to the vapors. Copper in both the liquid and vapor environments also sustained damage, but corrosion rates were slower. Steel corroded very slowly while immersed in the liquid mixture; the NIST paper suggests bacteria may have created a biofilm that was protective in this case.

Although copper corroded slowly—it would take about 15 years for 1.2-millimeter-thick copper tube walls to develop holes—localized corrosion was observed on cold-worked copper, the material used in sump pump tubing, NIST co-author Elisabeth Mansfield notes. Therefore, stress-corrosion cracking is a concern for bent copper tubing because it would greatly reduce tube lifetime and result in leaks.

The NIST test equipment developed for the study could be used in future investigations of special coatings and biocides or other ways to prevent sump pump failures and leaks.

Explore further: NIST develops prototype meter test for hydrogen refueling stations

More information: J.W. Sowards and E. Mansfield. "Corrosion of copper and steel alloys in a simulated underground storage tank sump environment containing acid producing bacteria." Corrosion Science. July, 2014. In press, corrected proof available online. DOI: 10.1016/j.corsci.2014.07.009

add to favorites email to friend print save as pdf

Related Stories

Recommended for you

Off-world manufacturing is a go with space printer

20 hours ago

On Friday, the BBC reported on a NASA email exchange with a space station which involved astronauts on the International Space Station using their 3-D printer to make a wrench from instructions sent up in ...

First drone in Nevada test program crashes in demo

Dec 19, 2014

A drone testing program in Nevada is off to a bumpy start after the first unmanned aircraft authorized to fly without Federal Aviation Administration supervision crashed during a ceremony in Boulder City.

Fully automated: Thousands of blood samples every hour

Dec 19, 2014

Siemens is supplying automation technology for the longest and one of the most cutting-edge sample processing lines in any clinical laboratory. The line, or automation track, 200 meters long, in Marlborough, ...

Explainer: What is 4-D printing?

Dec 19, 2014

Additive manufacturing – or 3D printing – is 30 years old this year. Today, it's found not just in industry but in households, as the price of 3D printers has fallen below US$1,000. Knowing you can p ...

User comments : 3

Adjust slider to filter visible comments by rank

Display comments: newest first

24volts
5 / 5 (1) Jul 30, 2014
More good reasons alcohol should not be in gasoline. It causes nothing but problems.
Dr_toad
Jul 30, 2014
This comment has been removed by a moderator.
24volts
5 / 5 (1) Jul 30, 2014
I totally agree with that. Grilled on the cobb is pretty good too though.
Whydening Gyre
not rated yet Jul 31, 2014
Corn is better in Bourbon. And Bourbon is better in me. ;)

You call it corn... We call it a"maize"ing...

Please sign in to add a comment. Registration is free, and takes less than a minute. Read more

Click here to reset your password.
Sign in to get notified via email when new comments are made.